Release Notes

2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has twenty-one (21) IEC-320-C13 outlets and six (6) IEC-320-C19 outlets.
P
OWER CORD The Rack PDU has a 3-m (10-ft) NEMA, 4-pin L15-30P power cord.
WG8H2
Electrical
Input connection NEMA, 4-pin L15-30P
Acceptable input voltage 208 VAC
± 10%, 3-phase
Maximum input current (phase) 24 A (derated)
Input frequency 50/60 Hz
Input power 8.6 kVA
Output voltage 208 VAC (Line-to-Line)
Output connections Twenty-one (21) IEC-320-C13;
Six (6) IEC-320-C19
Maximum output current (outlet) IEC-320-C13: 12 A; IEC-320-C19: 16 A
Maximum output current (bank) 16 A (derated)
Overload protection (internal) Three (3) 20 A 2-pole hydraulic-magnetic circuit
breakers
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.6 cm
(64.0 x 2.2 x 1.7 in)
Depth at breakers: 9.4 cm (3.7 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight 6.5 kg (14.2 lb)
Shipping weight 8.3 kg (18.2 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing