2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has seven (7) C13 and two (2) C19 outlets.
P
OWER CORD The Rack PDU has a IEC-320 C20 inlet and can be used with a detached power cord (not provided).
G789N
Electrical
Input connection IEC-320 C20 inlet
Acceptable input voltage 100–240 VAC
± 10% (UL(C-UL)/PSE)
200–240 VAC +6% to -10% (International)
Maximum input current (phase) 16 A (UL(C-UL) derated/International)
20 A (PSE)
Input frequency 50/60 Hz
Output voltage 100–240 VAC
± 10% (UL(C-UL)/PSE)
200–240 VAC +6% to -10% (International)
Output connections (7) C13 and (2) C19
Maximum output current (outlet) C19; 16 A, C13; 12 A (UL(C-UL) derated)
C19; 20 A, C13; 15 A (PSE)
C19; 16 A, C13; 10 A (International)
Maximum output current (phase) 16 A (UL(C-UL) derated/International)
20 A (PSE)
Physical
Dimensions
(H x W x D)
38.81 x 4.36 x 9.29 cm
(15.28 x 1.72 x 3.66 in)
Shipping dimensions
(H x W x D)
43.61 x 21.03 x 7.59 cm
(17.17 x 8.28 x 2.99 in)
Weight 1.56 kg (3.43 lb)
Shipping weight 2.00 kg (4.44 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals VDE, IRAM, SABS, GOST-R, PSE,
SONCAP, KC, CE, UL(C-UL)
ROHS Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision