Quick Reference Guide

cfgChassisMaxPowerConservationMode (Read/Write)
Description Enables or disables maximum power conservation mode. When enabled, all servers
are immediately reduced to their minimum power levels, and all subsequent server
power allocation requests are denied. In this mode, performance of powered on
servers may be degraded, and additional servers cannot be powered on, regardless
of server priority.
Legal Values
0 (disabled)
1 (enabled)
Default 0 (disabled)
cfgChassisPerformanceOverRedundancy (Read/Write)
Description Enables or disables server performance over power
redundancy. When enabled, this option favors server
performance and server powerup, over maintaining power
redundancy. When disabled, the system favors power
redundancy over server performance. When disabled,
then if the power supplies in the chassis do not provide
sufficient power, both for redundancy, as well as full
performance, then some servers may not be granted
sufficient power for full performance, or may not be
powered on, in order to maintain redundancy.
Legal Values
0 (disabled)
1 (enabled)
Default 1 (enabled)
cfgChassisInMaxPowerCapacity (Read Only)
Description Indicates the total chassis power budget (in watts) available for chassis operation.
Legal Values None
Default None
cfgChassisInRedundancyReserve (Read Only)
Description Indicates the amount of redundant power (in watts) in reserve that can be utilized in
the event if an AC grid or PSU is unsuccessful. This value is 0 if the Redundancy Policy
is set to 0 (no redundancy).
Legal Values 0 (disabled)
1 (enabled)
Default None
191