2 Dell Managed Rack Power Distribution Unit—Product Specifications
Product Specifications
The Dell Managed Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19 outlets.
P
OWER CORD The 3.0 m (10 ft) power cord terminates
with a 32 A, IEC-309 5-pin plug [530P6W/532P6W (Intl/NA)].
K539N
Electrical
Input connection 32 A, IEC-309 5-pin plug
Acceptable input voltage 380 - 415 VAC +6%, -10%, 3-phase
Maximum input current (phase) 32 A International; 24 A UL, C-UL (derated)
Input frequency 50/60 Hz
Input power 22.1 kVA International
17.2 UL, C-UL (derated)
Output voltage 220 - 240 VAC (Line-to-Neutral)
Output connections Twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19
Maximum output current (outlet) IEC-320-C13: 10 A; IEC-320-C19: 16 A International
IEC-320-C13: 12.8 A; IEC-320-C19: 12.8 A UL, C-UL
Maximum output current (phase) 32 A International; 24 A UL, C-UL (derated)
Maximum output current (breaker) 16 A International;
12.8 A UL, C-UL (derated)
Overload protection (internal) Six (6) 16 A, 1-pole hydraulic-magnetic circuit breakers
Physical
Dimensions
(H x W x D)
182.9 x 5.6 x 5.5 cm
(72.0 x 2.2 x 2.16 in)
Depth at breakers: 9.4 cm (3.7 in.)
Shipping dimensions
(H x W x D)
207.9 x 22.5 x 15.6 cm
(81.9 x 8.9 x 6.1 in)
Weight 8.9 kg (19.5 lb)
Shipping weight 10.7 kg (23.5 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3 048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing