Release Notes

www.dell.com | support.dell.com
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
O
UTLETS—The Rack PDU has (42) IEC 320-C13 outlets.
P
OWER CORD—The Rack PDU attached power cord terminates with a 5-pin, 3f, IEC60309 plug, 530P6S or 532P6S.
DELLM0005
Electrical
Input connection
NA: IEC60309-30 A plug ; INTL: IEC60309-32 A plug
Acceptable input voltage 346–415 VAC ± 10%
Maximum input current (phase) NA: 30 A (24 A UL(C-UL) derated); INTL: 32 A
Input power 22 kVA
Input frequency 50/60 Hz
Output voltage 200–240 VAC ± 10%
Output connections (42) IEC 320-C13
Maximum output current (outlet) C13: 10 A
Maximum output current (phase) NA: 30 A (24 A UL(C-UL) derated); INTL: 32 A
Maximum output current (total all
output)
NA: 72 A (maximum); INTL: 96 A (maximum)
Maximum output current
(breaker)
20 A
Physical
Dimensions
(H
W D)
178.0 5.6 5.1 cm
(70.1
2.2 2.0 in)
Depth at breakers: 9.3 cm (3.7 in)
Shipping dimensions
(H
W D)
200.0 20.0 17.0 cm
(78.7
7.9 6.7 in)
Weight 7.0 kg (15.4 lb)
Shipping weight 9.4 kg (20.7 lb)
Information in this document is subject to change without notice.
© 2010–2012 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in
trademarks and trade names other than its own.
Model DELLM0005
2/2012 • 164202134 Rev 2