User guide

2 Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has twenty (20) IEC-320-C13 outlets and six (6) IEC-320-C19 outlets.
P
OWER CORD The Rack PDU has a 32 A, 3-pin IEC-309 power cord.
G744N
Electrical
Input connection 32 A, 3-pin IEC-309
Acceptable input voltage 220–240 VAC +6%, -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Input power 7.7 kVA
Output voltage 220–240 VAC (Line-to-Neutral)
Output connections Twenty (20) IEC-320-C13;
Six (6) IEC-320-C19
Maximum output current (outlet) IEC-320-C13: 10 A; IEC-320-C19: 16 A
Maximum output current (phase) 32 A
Maximum output current (breaker) 16 A
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.6 cm
(64.0 x 2.2 x 1.7 in)
Depth at breakers: 9.4 cm (3.7 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight 6.2 kg (13.6 lb)
Shipping weight 8.0 kg (17.6 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing