User Manual

1-4 Cabling Instructions for the –48 VDC
www.dell.com | support.dell.com
Assembling the Safety Ground Wire
1 Strip the insulation from the end of the green/yellow wire, exposing approximately
4.5 mm (0.175 inches) of copper wire.
2 Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire.
Connecting the –48 VDC Power Cable and
Safety Ground
1 Connect the safety ground to the grounding post on the back of the system using a
#6-32 nut equipped with a locking washer (see Figure 1-2).
2 Plug the DC power cable into the system.
Figure 1-2. Safety Ground
safety ground
grounding post
lock washer
#6-32 nut