Users Guide

Object Description Usage Example
MFSMinimumL
imit
Read Minimum limit for MFS
Values from 0 to
MFSMaximumLimi
t
Default is 255
(means None)
To display the lowest value that can
be set using MinimumFanSpeed
option.
racadm get
system.thermalsettings.MFSM
inimumLimit
MinimumFanS
peed
Allows configuring the
Minimum Fan speed that
is required for the system
to operate.
It defines the baseline
(floor) value for fan speed
and system allows fans to
go lower than this
defined fan speed value.
This value is %PWM value
for fan speed.
Values from
MFSMinimumLimi
t to
MFSMaximumLimi
t
When get
command reports
255, it means user
configured offset
is not applied.
To make sure that the system
minimum speed does not decrease
lower than 45% PWM (45 must be a
value between MFSMinimumLimit
to MFSMaximumLimit):
racadm set
system.thermalsettings.Mini
mumFanSpeed 45
ThermalProf
ile
Allows you to specify the
Thermal Base Algorithm.
Allows you to set the
system profile as required
for thermal behavior
associated to the profile.
Values:
0 — Auto
1 — Maximum
performance
2 — Minimum
Power
To view the existing thermal profile
setting:
racadm get
system.thermalsettings.Ther
malProfile
To set the thermal profile to
Maximum Performance:
racadm set
system.thermalsettings.Ther
malProfile 1
ThirdPartyP
CIFanRespon
se
Thermal overrides for
third-party PCI cards.
Allows you to disable or
enable the default system
fan response for detected
third-party PCI cards.
You can confirm the
presence of third-party
PCI card by viewing the
message ID PCI3018 in
the Lifecycle Controller
log.
Values:
1— Enabled
0— Disabled
NOTE: The
default value
is 1.
To disable any default fan speed
response set for a detected third-
party PCI card: racadm set
system.thermalsettings.Thir
dPartyPCIFanResponse 0
Modifying thermal settings using iDRAC settings utility
To modify the thermal settings:
1. In the iDRAC Settings utility, go to Thermal.
The iDRAC Settings Thermal page is displayed.
2. Specify the following:
Thermal Profile
Maximum Exhaust Temperature Limit
64