Owners Manual

About this task
Install the 1U cable management tray into a rack with a depth of 1070 mm (42.1 in.).
Steps
1 The 1U cable management tray rails are shipped with alignment pins that are designed to ๎št into a standard rack.
To install the rails in a non-standard rack, remove the alignment pins from the rails and install the appropriate square hole or threaded
hole alignment pins.
a Using a ๎š…at-head screwdriver, remove the alignment pins from the front and back of the rails.
b Identify the appropriate alignment pins (square hole or threaded hole) to use in the non-standard rack
c Install the appropriate alignment pins onto front and back of the rails.
2 Align the rails so that the UP arrow is pointed in the correct direction and the side of the rail labeled FRONT is at the front of the rack.
3 Insert the alignment pins of left and right rails into the mounting holes at the front and back of the rack.
4 Secure the rails by installing 8-32 x 0.75 in. screws into the holes at the front and back of the rails.
Figure 7. Secure Rails to Rack
5 Align the 1U cable management tray so that the UP arrow is pointed in the correct direction and the side of the tray labeled FRONT is
to the front of the rack.
Figure 8. Align the Cable Management Tray
6 Slide the 1U cable management tray into the rails until it locks into place.
SC460 Expansion Enclosure Installation
15