User Manual

Table Of Contents
44
|
Operation
Table 4. Operating Mode Status Icons (continued)
Description
Icon Mode
Converter Mode The UPS inverter supplies the load from utility power while
acting as a frequency converter, locking the UPS into a stable
output frequency and transferring to Battery mode as necessary.
However, the input and output frequency are not synchronized.
Bypass mode is not available.
NOTE: Use Converter mode to lock the UPS output frequency
at 50 Hz or 60 Hz to suit power-sensitive equipment, or to
provide 50 Hz output when the available standard utility input is
60 Hz (or the reverse).
Standby Mode When the UPS is turned off and remains connected to utility
power, the UPS is in Standby mode and utility power supplies
the connected equipment. The UPS is not supporting the load,
but is ready to assume the load on command.
Active Notices and Alarms
The notice and alarm screens are visible only when notices or alarms are active. There is a separate
status summary screen for each active notice or alarm. If there are no active notices or alarms, a “No
Active Alarms” message appears in a single screen between the UPS status summary and the battery
status screen. If there are multiple notices or alarms, scroll through each notice or alarm screen to reach
the first battery status screen.
NOTE:
Events are not shown in status summary screens. They appear only in the Event Log.
Battery Operating Status
Table 5 describes the available battery operating status notifications that are provided on status
summary screens. Only one battery operating status is reported at a time.