Operation
Table 7. Settings (continued)
Description Default SettingAvailable Settings
Automatic Start Delay [Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 57.
0s: Load Segment 1
(LS1)
1s: Load Segment 2
(LS2)
Automatic on Battery Shutdown [Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 57.
Off
Start on Battery [Enabled] [Disabled]
NOTE: Battery start is disabled from the factory and
remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. If this is set
by the user, it remains set.
Enabled
Battery Saving Mode [Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
Disabled
On Battery Notice Delay [0s] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
0s
Site Wiring Fault Alarm [Enabled] [Disabled] Disabled
Bypass Voltage Low Limit [-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).
NOTE: The Qualify Bypass setting may overrule the
Bypass Voltage Low Limit setting.
-15% of nominal
Bypass Voltage High Limit [+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).
NOTE: The Qualify Bypass setting may overrule the
Bypass Voltage High Limit setting.
+10% of nominal