Operation
Table 7. Settings (continued)
Description Default SettingAvailable Settings
Charger [Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
Enabled
Battery Charge % to Restart [0%] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0%, the feature is disabled.
0%
Battery Low Alarm [Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.
3 min
Automatic Battery Support Tests [Enabled] [Disabled]
See “Running Automatic Battery Tests” on page 61.
Enabled
Reset Peak Consumption Watts [No] [Yes]
If No, no action.
If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the current date and time.
No
Reset Cumulative Consumption
kWh
[No] [Yes]
If No, no action.
If Yes, the Cumulative Consumption kWh value is
cleared and the date and time stamp for this
statistic is set to the current date and time.
No
Reset Peak Headroom Watts [No] [Yes]
If No, no action.
If Yes, the Peak Headroom Watts value is cleared
and the date and time stamp for this statistic is set
to the current date and time.
No