User Manual

Table Of Contents
55
Operation
|
Table 8. UPS Behavior in Converter Mode
Load
Output
Frequency
Setting
Input Frequency
(Hz)
Output
Frequency
(Hz)
UPS Behavior
≤50% 50 Hz
47–53 47–53 UPS in Converter mode synchronizes the output
frequency with the input frequency.
45–46 or 54–65 50 UPS in Converter mode converts the input
frequency to 50 Hz output frequency
<45 or >65 50 UPS transfers to Battery mode to provide 50 Hz
output frequency.
60 Hz
57–63 57–63 UPS in Converter mode synchronizes the output
frequency with the input frequency.
45–56 or 64–65 50 UPS in Converter mode converts the input
frequency to 60 Hz output frequency.
<45 or >65 50 UPS transfers to Battery mode to provide 60 Hz
output frequency.
> 50% 50 Hz
47–53 47–53 UPS in Converter mode synchronizes the output
frequency with the input frequency.
45–46 or 54 -55 50 UPS in Converter mode converts the input
frequency to 50 Hz output frequency.
<45 or >55 50 UPS transfers to Battery mode to provide 50 Hz
output frequency.
60 Hz
57–63 57–63 UPS in Converter mode synchronizes the output
frequency with the input frequency.
55–56 or 64–65 50 UPS in Converter mode converts the input
frequency to 60 Hz output frequency.
<55 or >65 50 UPS transfers to Battery mode to provide 60 Hz
output frequency.