Specifications
Table 16. Battery
Configuration
10 kW: (24) 288V, 9.0 Ah internal batteries; EBM: (24) 288V, 9.0 Ah
Battery Type YUASA NPW 45-12 9.0 Ah
Voltage 10 kW: 288 Vdc internal; EBM : 288 Vdc/40A
Fuses UPS: (1) 80A fuses
EBM: (1) 80A fuses
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging 10 kW internal batteries: Approximately 4 hours to 90% usable capacity at nominal
line and no supplementary power supply load
EBM: Approximately 8 hours to 90% usable capacity at nominal line and no
supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Battery Runtimes* 10 kW internal batteries: 5 minutes at full load/14 minutes at half load
10 kW with one EBM attached: 13 minutes at full load/35 minutes at half load
* Battery runtimes are approximate and vary depending on the load configuration and battery charge.