MIB Objects
|
Table 11. IETF UPS MIB Objects (continued)
Variable Name and Relative XML Object Path Variable UnitVariable TypeOID
upsBypassNumLines
No Relative XML Object Path
1.5.2 Integer
upsBypassVoltage
UPS.PowerConverter.Input[2].Voltage
1.5.3.1.2 Integer V
upsBypassCurrent
UPS.PowerConverter.Input[2].Current
1.5.3.1.3 Integer 0.1A
upsBypassPower
No Relative XML Object Path
1.5.3.1.4 Integer W
upsAlarmsPresent
No Relative XML Object Path
1.6.1 Gauge
upsAlarmTable
No Relative XML Object Path
upsAlarmBatteryBad
UPS.PowerSummary.PresentStatus.NeedReplacement
1.6.3.1
upsAlarmOnBattery
UPS.PowerSummary.PresentStatus.Discharging
1.6.3.2
upsAlarmLowBattery
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit
1.6.3.3
upsAlarmDepletedBattery
Relative XML Object Path not implementated
1.6.3.4
upsAlarmTempBad
UPS.PowerSummary.PresentStatus.OverTemperature
1.6.3.5
upsAlarmInputBad
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange
1.6.3.6
upsAlarmOutputBad
Relative XML Object Path not implementated
1.6.3.7
upsAlarmOutputOverload
UPS.PowerSummary.PresentStatus.Overload
1.6.3.8
upsAlarmOnBypass
UPS.PowerConverter.Input[2].PresentStatus.Used
1.6.3.9
upsAlarmBypassBad
UPS.PowerConverter.Input[2].PresentStatus.Good
1.6.3.10
upsAlarmOutputOffAsRequested
Relative XML Object Path not implementated
1.6.3.11