62
|
MIB Objects
Table 11. IETF UPS MIB Objects (continued)
Variable Name and Relative XML Object Path Variable UnitVariable TypeOID
upsAlarmUpsOffAsRequested
Relative XML Object Path not implementated
1.6.3.12
upsAlarmChargerFailed
UPS.BatterySystem.Charger.PresentStatus.InternalFailure
1.6.3.13
upsAlarmUpsOutputOff
UPS.PowerSummary.PresentStatus.Good
1.6.3.14
upsAlarmUpsSystemOff
Relative XML Object Path not implementated
1.6.3.15
upsAlarmFanFailure
UPS.PowerSummary.PresentStatus.FanFailure
1.6.3.16
upsAlarmFuseFailure
UPS.BatterySystem.Battery.PresentStatus.FuseFault
UPS.PowerConverter.Input[1].PresentStatus.FuseFault
UPS.PowerConverter.Inverter.PresentStatus.FuseFault
1.6.3.17
upsAlarmGeneralFault
UPS.PowerSummary.PresentStatus.InternalFailure
1.6.3.18
upsAlarmDiagnosticTestFailed
Relative XML Object Path not implementated
1.6.3.19
upsAlarmCommunicationsLost
UPS.PowerSummary.PresentStatus.CommunicationLost
1.6.3.20
upsAlarmAwaitingPower
Relative XML Object Path not implementated
1.6.3.21
upsAlarmShutdownPending
UPS.PowerSummary.DelayBeforeShutdown
1.6.3.22
upsAlarmShutdownImminent
UPS.PowerSummary.PresentStatus.ShutdownImminent
1.6.3.23
upsTestResultsSummary
UPS.BatterySystem.Battery.Test
1.7.3 Integer {1,2,3,4,5,6}
upsShutdownType
No Relative XML Object Path
1.8.1 Integer Sec
upsShutdownAfterDelay
UPS.PowerSummary.DelayBeforeShutdown
1.8.2 Integer Sec
upsStartupAfterDelay
UPS.PowerSummary.DelayBeforeStartup
1.8.3 Integer Sec