Manual

66
|
MIB Objects
Product Physical Group
The name of the group is “Physical” with a group OID of 120. See Table 14 for OID 120 group
variables.
Table 14. Product Physical Group Variables
Variable Name and Description OID
Variable
Type
Variable
Unit
physicalIdentFamilyName
UPS Family name
UPS.PowerSummary.iProduct
1.1 String
physicalIdentSerialNumber
UPS Serial number
UPS.PowerSummary.iSerialNumber
1.2 String
physicalIdentConverterType
UPS type:Off Line / Line interactiveOn LineOn Line - Unitary/ParallelOn Line -
Parallel with NSOn Line - Hot Standby Redundancy (set on redundant UPS)
UPS.PowerConverter.ConverterType
1.3 Integer
physicalOutputInstantHeadroom
This is the present amount of watt capacity remaining before overload.
(Present Watts – Watts Rating of UPS = Headroom Watts)
UPS.PowerConverter.Output.RemainingActivePower
2.1 Integer Watts
physicalOutputPeakHeadroom
Statistical value holding the lowest value that Instantaneous Headroom Watts was ever
set to since the last time this statistic was reset
UPS.StatisticSystem.Output.Statistic[2].RemainingActivePower
2.2 Integer Watts
physicalOutputPeakHeadroomTimestamp
Time and date stamp of the last time the Peak Headroom Watts value was updated
UPS.StatisticSystem.Output.Statistic[2].Time
2.3 Integer Time
Stamp
physicalOutputPeakConsumption
Statistical value of the maximum RMS Watts the UPS has seen since the last time this
statistic was reset
UPS.StatisticSystem.Output.Statistic[3].ActivePower
2.4 Integer Watts
physicalOutputPeakConsumptionTimestamp
Time and date stamp of the last time the Peak Consumption Watts value was updated
UPS.StatisticSystem.Output.Statistic[2].Time
2.5 Integer Time