MIB Objects
|
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapInputFrequencyOutOfRangeOk
Input under or over frequency ok
UPS.PowerConverter.Input[1].PresentStatus.FrequencyOutOfRange = 0
16 1
trapRemoteEmergencyPowerOff
Remote emergency power off
UPS.PowerSummary.PresentStatus.EmergencyStop = 1
17 2
trapReturnFromEmergencyPowerOff
Return from remote emergency power off
UPS.PowerSummary.PresentStatus.EmergencyStop = 0
18 1
trapOutputOverload
Output overload
UPS.PowerSummary.PresentStatus.Overload = 1
19 2
trapOutputOverloadOk
Output overload ok
UPS.PowerSummary.PresentStatus.Overload = 0
20 1
trapLevel2Overload
Level 2 overload
UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 1
21 2
trapLevel2OverloadOk
Level 2 overload ok
UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 0
22 1
trapLevel3Overload
Level 3 overload
UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 1
23 3
trapLevel3OverloadOk
Level 3 overload ok
UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 0
24 1
trapPosDCLinkOverVoltage
Positive DC link over voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 1
25 2
trapPosDCLinkOverVoltageOk
Positive DC link over voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 0
26 1