MIB Objects
|
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapChargerOk
Charger ok
UPS.BatterySystem.Charger.PresentStatus.InternalFailure = 0
38 1
trapEepromFailure
EEPROM failure
UPS.PowerSummary.PresentStatus.ConfigurationFailure = 1
39 3
trapEepromOk
EEPROM ok
UPS.PowerSummary.PresentStatus.ConfigurationFailure = 0
40 1
trapShutdownImminent
Shutdown imminent
UPS.PowerSummary.PresentStatus.ShutdownImminent = 1
41 3
trapShutdownImminentOver
Shutdown imminent over
UPS.PowerSummary.PresentStatus.ShutdownImminent = 0
42 1
trapBatteryLow
Battery low
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit = 1
43 3
trapBatteryOk
Battery ok
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit = 0
44 1
trapOutputShortCircuit
Output short circuit
UPS.PowerConverter.Output.PresentStatus.ShortCircuit = 1
45 3
trapOutputReturnFromShortCircuit
Output return from short circuit
UPS.PowerConverter.Output.PresentStatus.ShortCircuit = 0
46 1
trapUtilityNotPresent
Utility not present
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange = 1
47 2
trapUtilityPresent
Utility present
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange = 0