Manual

74
|
MIB Objects
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapBatteryOverVoltage
Battery DC over voltage
UPS.BatterySystem.Battery.PresentStatus.VoltageTooHigh = 1
49 3
trapBatteryOverVoltageOk
Battery DC over voltage ok
UPS.BatterySystem.Battery.PresentStatus.VoltageTooHigh = 0
50 1
trapHeatsinkOvertemperature
Heatsink overtemperature
UPS.PowerSummary.PresentStatus.OverTemperature = 1
51 3
trapHeatsinkOvertemperatureOk
Heatsink overtemperature ok
UPS.PowerSummary.PresentStatus.OverTemperature = 0
52 1
trapBypassNotAvailable
Bypass not available (applies only to double-conversion models)
UPS.PowerConverter.Input[2].PresentStatus.Good = 0
53 2
trapBypassNotAvailableOk
Bypass not available ok
UPS.PowerConverter.Input[2].PresentStatus.Good = 1
54 1
trapUPSOnBattery
UPS on battery
UPS.PowerConverter.Input[3].PresentStatus Used = 1
57 1
trapUPSReturnFromBattery
UPS return from battery
UPS.PowerConverter.Input[3].PresentStatus Used = 0
58 1
trapUPSOnBypass
UPS on bypass (applies only to double-conversion models)
UPS.PowerConverter.Input[2].PresentStatus.Used = 1
59 1
trapUPSReturnFromBypass
UPS return from bypass
UPS.PowerConverter.Input[2].PresentStatus.Used = 0
60 1
trapBatteryTestInProgress
Battery manual or automatic test in progress
UPS.BatterySystem.Battery.Test = 5
61 1