User Manual

20
|
Installation and Startup
Installing the Input and Ground Wires
3 Punch a hole in the terminal block cover for the input conduit using a Greenlee
®
punch or similar
device. The hole accommodates 3 /4 or 1 IMC conduit.
4 Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach
a flexible metal fitting to the end of the conduit.
5 Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
Strip 0.5 (1 .5 cm) of insulation from the end of each incoming wire.
6 Connect the input and ground wires to the terminal block according to Table 1.
Table 1. UPS Wiring Specifications
Wire
Function
Terminal
Position
UPS Wire Function
Terminal Wire
Size Rating*
Tightening
Torque
Input
1 Input Ground
5.26–16 mm
2
(10–6 AWG)
2.26 Nm (20 lb in)
2 L2/Neutral In
3 L1 In
* Use 5.26 mm
2
(10 AWG) 75_C copper wire minimum.
7 Replace the terminal block cover.