Users Guide

60
|
MIB
11. IETF UPS MIB ()
변수 XML 체의  
변수변수 형식OID
upsEstimatedMinutesRemaining
UPS.PowerSummary.RunTimeToEmpty
1.2.3
upsEstimatedChargeRemaining
UPS.PowerSummary.RemainingCapacity
1.2.4 %
upsBatteryVoltage
UPS.PowerSummary.Voltage
1.2.5 0.1V
upsBatteryCurrent
UPS.PowerSummary.Current
1.2.6 0.1A
upsBatteryTemperature
UPS.BatterySystem.Battery.Temperature
1.2.7 °C
upsInputLineBads
XML 상대 없음
1.3.1 카운터
upsInputNumLines
XML 상대 없음
1.3.2
upsInputFrequency
UPS.PowerConverter.Input[1].Frequency
1.3.3.1.2 0.1 Hz
upsInputVoltage
UPS.PowerConverter.Input[1].Voltage
1.3.3.1.3 V
upsInputCurrent
UPS.PowerConverter.Input[1].Current
1.3.3.1.4 0.1 A
upsOutputSource
XML 상대 없음
1.4.1
upsOutputFrequency
UPS.PowerConverter.Output.Frequency
1.4.2 0.1 Hz
upsOuputNumLines
XML 상대 없음
1.4.3
upsOutputVoltage
UPS.PowerConverter.Output.Voltage
1.4.4.1.2 V
upsOutputCurrent
UPS.PowerConverter.Output.Current
1.4.4.1.3 0.1A
upsOutputPower
UPS.PowerConverter.Output.ActivePower
1.4.4.1.4 W
upsOutputPercentLoad
UPS.PowerSummary.PercentLoad
1.4.4.1.5 %