Specifications

50
STATUS CODE
-95
DESCRIPTION
No
MEMORY
RECALL
CONTROL
TYPE
TMM
Figure 1
User defined status code - see OEM instructions manual.
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 11 and 12 of TMM is at zero volts.
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 11 and 12 shorted to negative.
Defective input switch (shorted).
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PB1 and PB2 on pump
logic card.