Specifications

DVP201/202/211LC-SL Load Cell Module Operation Manual
4.1 Table of Control Registers
CR# Address Attribute Register name Explanation
#0 H1000 O R Model name
The model code of a load cell module is defined by
the module’s system.
DVP201LC-SL’s model code=H’5106
DVP202LC-SL’s model code=H’5206
DVP211LC-SL’s model code=H’5906
#1 H1001 O R Firmware version
Hexadecimal value
The current firmware version of a load cell module
is displayed.
#2 H1002 O R/W Characteristic value
CH1: Bit 0~bit 7; CH2: Bit 8~bit 15
Mode 0: 1 mV/V; Mode 4: 20 mV/V
Mode 1: 2 mV/V; Mode 5: 40 mV/V
Mode 2: 4 mV/V; Mode 6: 80 mV/V
Mode 3: 6 mV/V
#3 H1003 O R/W
Reaction time for
measurement
CH1: bit0~bit7; CH2: bit8~bit15
Mode 0: 2.5ms; Mode 5: 60ms
Mode 1: 10ms; Mode 6: 100ms
Mode 2: 16ms; Mode 7: 200ms
Mode 3: 20ms; Mode 8: 400ms
Mode 4: 50ms (factory setting)
#6 H1006 X R/W
Returning to
zero/Subtracting a tare
K1: Subtracting the tare
measured by CH1
K2: Not subtracting the
tare measured by CH1
K3: Restoring the weight
measured by CH1 to
zero
K4: Subtracting the tare
measured by CH2
K5: Not subtracting the
tare measured by CH2
K6: Restoring the weight
measured by CH2 to
zero
#7 H1007 O R/W
Displaying a gross
weight/net weight
CH1: Bit 0~bit 7; CH2: Bit 8~bit 15
K0: Displaying a gross weight
K1: Displaying a net weight
#8 H1008 O R/W
Tare measured by CH1
(Low word)
#9 H1009 O R/W
Tare measured by CH1
(High word)
#10 H100A O R/W
Tare measured by CH2
(Low word)
#11 H100B O R/W
Tare measured by CH2
(High word)
Displaying a tare
#12 H100C X R
Weight measured by CH1
(Low word)
#13 H100D X R
Weight measured by CH1
(High word)
#14 H100E X R
Weight measured by C2
(Low word)
#15 H100F X R
Weight measured by C2
(High word)
Displaying a weight
#16 H1010 O R/W
Number of weights
measured by CH1 in a
stability range
Setting range: K1~K500 (Factory setting: K5)
#17 H1011 O R/W
Number of weights
measured by CH2 in a
stability range
Setting range: K1~K500 (Factory setting: K5)
#18 H1012 O R/W Stability range for CH1 Setting range: K1~K10000 (Factory setting: K10)
#19 H1013 O R/W Stability range for CH2 Setting range: K1~K10000 (Factory setting: K10)
4-2