DVP201/202/211LC-SL Load Cell Module Operation Manual
5.2 Example 1
Example: One point is adjusted. (A weight which weighs 1 kg corresponds to 1000 lsb.)
A load cell module is directly connected to the left side of a DVP series PLC. The instruction TO is used to make
adjustment. The steps in making adjustment are as follows.
Step 1: Write K2 to CR#25. Please see the WPLSoft program shown below.
Step 2: Connect a load cell to a module, and put no load on the load cell.
Step 3: Write H’0001 to CR#26. Please see the WPLSoft program shown below.
Step 4: Select point 1 (default setting), and write H1 to CR#27. Please see the WPLSoft program shown below.
Step 5: Put a standard weight which weighs 1000 g on the load cell.
Standard weight (1 kg)
Step 6: Write K1000 (1000 g) to CR#33.
5-4