DIRECT-VENT FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUAL CD32M CD32M-1 CD32M-2 32" DV Fireplace with Fan 32" DV Fireplace 32" DV Fireplace with Fan & Door Switch CD36M-A CD36M-A1 CD36M-A2 36" DV Fireplace with Fan 36" DV Fireplace 36" DV Fireplace with Fan & Door Switch CD42M-A CD42M-A2 42" DV Fireplace with Fan 42" DV Fireplace with Fan & Door Switch WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or lo
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency or the gas supplier. WARNING: This direct-vent gas fireplace is intended for use with natural or propane/LP gas only. Do not attempt to burn any solid fuels in this appliance. This fireplace is manufactured for Stylecrest Inc.
INTRODUCTION WARNING: This product contains and/or generates chemicals known to the State of California to cause cancer or birth defects or other reproductive harm. Models CD32M series, CD36M-A series and CD42M-A series are heat circulating gravity direct-vent fireplaces with sealed combustion chamber. These fireplaces use millivolt gas control valve and millivolt ignition system. These fireplaces are convertible with the standard setup as natural gas. Conversion may be performed by the O.E.M.
SELECTING LOCATION Continued • Do not locate appliance close to where gasoline or other flammable liquids may be stored. The appliance must be kept clear and free from combustible materials. • Do not use this appliance if any part has been under water. Immediately contact a local service technician to examine the appliance and to replace any part(s) of the control ignition system and other related components that have been submerged under water.
PRE-INSTALLATION PREPARATION Continued VENT TERMINATION CLEARANCES The final position of your fireplace depends on the location of the vent termination in relation to the clearances that must be observed as shown in Figure 5 on page 6. The vent system serves as the “chimney” as well as the combustion air supply (air intake). The horizontal run must have a rise of 1/4" (.6 cm) for every 12" (30.48 cm) of horizontal run towards the termination.
PRE-INSTALLATION PREPARATION Continued N N D H V L E B C Fixed Closed F B Openable Fixed Closed V Openable V I V G B V B B J X V G G M A V K X V A G GAS METER RESTRICTED AREA V TERMINATION CAP X AIR SUPPLY INLET (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony I = clearance to service regulator vent outlet [*72 inches (182.9cm) [*12 inches (30.
INSTALLATION WARNING: Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life. NOTICE: Failure to follow these instructions will void the warranty. VENTING INSTALLATION PRECAUTIONS Consult local building codes before beginning the installation.
INSTALLATION Continued 6. For vertical installation, a vertical termination is available. Also for vertical venting application, install vertical flue restrictor into inner collar of fireplace as shown in Figure 6, page 7. When installing a length of pipe for vertical termination that is over 3 ft., support the pipe every 3 ft. using metal wall straps. Vertical to horizontal pipe must be kept at a 1 ft. to 4 ft. ratio with a maximum run of no more than 20 ft.
INSTALLATION Continued ELECTRICAL HOOKUP AND REMOTE RECEIVER DIAGRAM An outlet box with two receptacles (see Figure 9) has been supplied for your convenience and is located inside on the lower right side of the fireplace. The remote control receiver is factory wired and connected to the convertible gas valve as shown in Figure 10.
INSTALLATION Incoming 1/2" Gas Line Permitted By Local Codes Continued In conformance with local codes, route a 1/2" NPT gas line towards the appliance coming in from either the left or right side of the fireplace (see Figure 13). Install a sediment trap between the incoming gas line and the gas control box (see Figure 14). The sediment trap should extend down a minimum of 3" (7.62 cm) beyond the center of the pipe.
INSTALLATION Continued 3. Undo latches located on top and bottom of firebox (see Figure 17). Carefully swing door to the left. The glass door is securely mounted to the firebox with 5 screws.
INSTALLATION Continued 5. Place log #5 (small front log) onto the front left part of grate making sure notches fit over prongs of grate (see Figure 22). 6. Place log #6 onto two pins on left side of back and front logs (see Figure 22). 6 5. Place log #5 (top log) onto right pin of front log (#2) and smooth surface of rear log (#3). Make sure it is seated properly (see Figure 27). 6. Place log #6 (left log) on left pin of front log (#2) and smooth surface of rear log (#3).
INSTALLATION Continued Lava Rock and Ember Material 1. For all models, place lava rock along sides and front of firebox bottom in areas that are visible. It is not necessary to use all lava rock provided. 3. Align holes on right face extension with holes on right side of front face assembly and secure with screws previously removed (see Figure 29). Do the same for left side. 4. Secure top face extension with left and right face extensions with two sheet metal screws (see Figure 29).
OPERATING FIREPLACE BURNER FLAME ADJUSTMENT OPERATION GUIDELINES Continued If adjustment is necessary, you can restore the proper flame setting by loosening the air shutter screw and rotating the air shutter until proper setting is achieved (see Figure 31). The correct shutter openings are as follows: Tube Burner Model CD32M Pan Burner Natural Propane/ Natural Propane/ LP LP 0.188" Max. — CD36M-A 0.188" Max — — — CD42M-A 0.188" 0.313" 0.188" 0.
OPERATING FIREPLACE Continued Thermocouple Piezo Ignitor Pilot Burner Thermopile D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. LIGHTING INSTRUCTIONS Figure 33 - Pilot 1. STOP! Read the safety information above before proceeding. 2. Set the “HI-LO” knob to the lowest setting. 3.
CONVERTING FIREPLACE FROM NATURAL GAS TO PROPANE/LP GAS 3. Install the identification label enclosed with gas valve regulator to the valve body where it can easily be seen (see Figure 36). Continued WARNING: The conversion kit must be installed by a qualified service technician in accordance with the manufacturers instructions and all applicable codes and requirements of the authority having jurisdiction.
TROUBLESHOOTING WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater. WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater. OBSERVED PROBLEM POSSIBLE CAUSE REMEDY Pilot will not stay lit 1. Defective thermocouple 1. Check pilot flame. It must impinge on thermocouple 2. Clean or adjust pilot for maximum flame impingement on thermocouple 3.
ILLUSTRATED PARTS BREAKDOWN MODELS CD32M AND CD36M-A SERIES 21-3 21-4 21-5 21-6 6 7 8 21-2 21-1 20 1 4 3 13 9 16 19 18 14 11 17 10 38 22 12 37 36 15 23 39 34 29 2 24 28 15 5 30 35 27 25 42 32 33 26 31 41 40 18 www.desatech.
PARTS LIST MODELS CD32M AND CD36M-A SERIES KEY NO.
ILLUSTRATED PARTS BREAKDOWN MODEL CD42M-A 6 7 8 20 21-5 1 21-4 13 21-7 21-6 21-3 212 21-1 3 17 11 10 9 19 12 18 16 2 37 23 14 41 15 15 42 36 4 5 38 22 40 39 35 29 28 32 34 24 31 30 27 26 28 25 20 www.desatech.
PARTS LIST MODEL CD42M-A KEY NO.
SPECIFICATIONS CD32M CD36M-A CD42M-A Gas Rate (Natural) 12,000/ 18,000 Btu/hr 15,000/ 22,000 Btu/hr 25,000/ 35,000 Btu/hr Gas Rate (Propane/LP) 11,000/ 17,000 Btu/hr 14,000/ 20,000 Btu/hr 23,000/ 33,000 Btu/hr Ignition Piezo Piezo Piezo Natural Gas Manifold Pressure 3.5" w.c. 3.5" w.c. 3.5"w.c. Propane/LP Manifold Pressure 10" w.c. 10" w.c. 10" w.c. Minimum Inlet Supply Pressure 4.5" w.c. 4.5" w.c. 4.5" w.c.
ACCESSORY AND REPLACEMENT PARTS MILLIVOLT PI L OT LOT PI ON TH O FF TPTH TP HI-LO VALVE P/N #14389 REGULAR BLOWER KIT BK FOR MODELS CD32M, CD32M-2 CD36M-A, CD36M-A2 AND CD42M-A STANDARD TOP LOUVER P/N 108903-01 (CD32M SERIES) P/N 108011-01 (CD36M-A SERIES) P/N 108331-01 (CD42M-A) PILOT ASSY.