29. Verify that the control and high limit sensor thermocouples are connected.
Table 12. Sensor Calibration Page Parameters and Values.
Menu Item
Display
Description
Range
Control
Sensor Cal
Ctrl Sens -100F
Ctrl Sens 1400F
Ctrl Sens Done
Calibrate Sensor Low End
Calibrate Sensor High End
Control Sensor Cal
Complete
-100 to 1400°F
-100 to 1400°F
(read only)
HiLim Sensor
Cal
HL Sens -100F
HL Sens 1400F
HL Sens Done
Calibrate HiLim Sensor Low
End
Calibrate HiLim Sensor High
End
HiLim Sensor Cal Complete
-100 to 1400°F
-100 to 1400°F
(read only)
Retransmit
Cal
RetCalLo XXXX
17
17
RetCalHi XXXX
Calibrate Retransmit Output
Low
Calibrate Retransmit Output
High
0 to 4096
0 to 4096
5.6.11. Setting up the Enable Page
The Enable Page controls access to the other Setup Pages when Level 1 Password is used.
The setpoint minimum and maximum values, and the security passwords are also set on
the Enable Page. Table 13 shows the menu items available.
5.6.11.1. Access Enable Page
1. Enter Setup Mode using a level 2 access code (See Section 5.6 for more on using
access codes).
2. Press Page until Enable displays.
3. Press
Menu.
4. Change each parameter by pressing
Menu until the desired parameter is displayed,
and then press ▲ or ▼ to change the value.
O
Changing Enable to Yes for each page will allow access to the
page in Level 1 security.
17
The RetCalLoand RetCalHivalues are only change indicators. The actual value is not meaningful.