8.1.12. Enable Page Default Values
Menu Item
Display
Default
Range
Setting
Profiles
Enable Profile 1-8
Yes
Yes or No
Autostart
Enable Auto Start
No
Yes or No
33
PID
Enable PID
Yes
Yes or No
Control
Enable Control
No
Yes or No
Communication
Enable Communication
No
Yes or No
33
Real Time Clock
Enable Clock
No
Yes or No
33
Relay outputs
Enable Relay 1-4
No
Yes or No
33
Test
Enable Test
No
Yes or No
Zone Calibration
Enable Zone Cal
No
Yes or No
Sensor Calibration
Enable Sensor Cal
No
Yes or No
Setpoint lower limit
Enable SPLowerLim
20°C
-73°C to 759°C (-100°F to
1399°F)
Setpoint upper limit
Enable SPUpperLim
260°C
-73°C to 760°C (-100°F to
1400°F)
High limit overhead
Enable HiLimOH
5°C
3 to 11°C (5 to 20°F)
34
Password level 1
Enable Password 1
1
0 to 999
Password level 2
Enable Password 2
2
0 to 999
Manual/Timer mode
setpoint change
Enable SPChange
Yes
Yes or No
Analog Output Type
Enable Analog Type
Proc
Ctrl or Proc
33
If the controller does not have this feature, No is the only option.
34
Maximum high limit setpoint (MaxHiLimSP) = SPUpperLim + HiLimOH. Minimum high limit
setpoint (MinHiLimSP) = SPLowerLim + HiLimOH.