ATTENTION!
Danger of damage to property!
If impermissible media are pumped, the pump may be destroyed.
Table 5.2:
Minimum inlet pressure (above atmospheric pressure) at the inlet
stub to prevent cavitation noise (with medium temperature T1)
Table 5.3:
The values are valid up to 300 m above sea level; the values
above this height are higher: 0.01 bar/100 m added height.
5.3 Scope of supply
Pump, complete
Installation and operating instructions
2 x flat gasket
Coupling relay
EMC (electromagnetic compatibility) General EMC: EN 61800-3
Emitted interference EN 61000-6-3, formerly EN 50081-1 (building standard)
Interference immunity EN 61000-6-2, formerly EN 50082-2 (industry standard)
Motor protection Integrated motor protection as standard
Fault current 3.5 mA
1. Observe the manufacturer's specifications regarding mixing ratios. Add any additives to the medium to be pumped on the pressure side of the pump.
Permissible medium
temperature
Permissible max. ambient temperature
-10 °C ... +95 °C + 40 °C
-10 °C ... +90 °C + 50 °C
-10 °C ... +80 °C + 55 °C
-10 °C ... +70 °C + 60 °C
-10 °C ... +65 °C + 65 °C
Nominal width
T
Med
T
Med
-10 °C...+50 °C +95 °C
Rp ½; Rp ¾; Rp 1; Rp 1¼ 0.3 bar 1.0 bar