Operating instructions
EN-3 452115.66.16 FD 9206 www.dimplex.de
UPE 70-25 - UPE 120-32
English
ATTENTION!
Danger of damage to property!
If impermissible media are pumped, the pump may be destroyed.
Table 5.2:
Minimum inlet pressure (above atmospheric pressure) at the inlet
stub to prevent cavitation noise (with medium temperature T1)
Table 5.3:
The values are valid up to 300 m above sea level; the values
above this height are higher: 0.01 bar/100 m added height.
5.3 Scope of supply
Pump, complete
Installation and operating instructions
2 x flat gasket
Coupling relay
EMC (electromagnetic compatibility) General EMC: EN 61800-3
Emitted interference EN 61000-6-3, formerly EN 50081-1 (building standard)
Interference immunity EN 61000-6-2, formerly EN 50082-2 (industry standard)
Motor protection Integrated motor protection as standard
Fault current 3.5 mA
1. Observe the manufacturer's specifications regarding mixing ratios. Add any additives to the medium to be pumped on the pressure side of the pump.
Permissible medium
temperature
Permissible max. ambient temperature
-10 °C ... +95 °C + 40 °C
-10 °C ... +90 °C + 50 °C
-10 °C ... +80 °C + 55 °C
-10 °C ... +70 °C + 60 °C
-10 °C ... +65 °C + 65 °C
Nominal width
T
Med
T
Med
-10 °C...+50 °C +95 °C
Rp ½; Rp ¾; Rp 1; Rp 1¼ 0.3 bar 1.0 bar