Operating instructions

www.dimplex.de 452115.66.16 FD 9206 EN-6
UPE 70-25 - UPE 120-32
English
7.2 Electrical connection
ATTENTION!
WARNING! Danger of electric shock
The electrical connection must be made by an electrician approved by the
local utility company in accordance with the locally valid regulations (e.g.
VDE regulations).
The mains connecting cable (Fig. 1.1 Appendix page II item
8) is inseparably connected to the pump.
ATTENTION!
Caution! Danger of damage to the pump
The cable must be connected in the factory. A subsequent connection is
not possible.
ATTENTION!
Warning! Danger of electric shock!
If the cable has been disconnected from the pump by force, there is
danger of personal injury:
When the pump is in generator operation (with the rotor driven), a
dangerous voltage may be present at the module contacts.
Do not stick any sharp objects (nails, screwdrivers, wire etc.) into the
module contacts.
The free end must be connected in the system's switch box (Fig.
4.1 Appendix page IV).
Black/brown flexible wire: L1 (phase)
Blue flexible wire: N (neutral conductor)
Green-yellow flexible wire: (protective earth)
The mains connection cable must be routed into the
system's switch box using a strain relief. The strain relief and
impermeability against dripping water/condensate must be
ensured. If necessary, the cable must be furnished with a
drip-off loop in order to prevent water from entering the
switch box.
The following minimum requirements must be fulfilled in the
event of a switch-off via an external/on-site circuit relay:
Nominal current > 10 A
Nominal voltage 250 V AC
Leakage current per pump I
eff
3.5 mA (according to EN
60335)
No on-site motor protection switch is necessary. If a motor
protection switch is already part of the system, this must be
bypassed or set to the maximum possible current value.
The pump can be protected using a fault current protection
switch.
Fault current designation: or
Current type and voltage of the mains connection must be in
accordance with the specifications on the type plate.
Mains connection voltage: 1 ~ 230 V, 50/60 Hz, DIN IEC
60038.
Line side fuse protection: See type plate,
The pump/system must be earthed according to regulations.
ATTENTION!
CAUTION! Danger of damage to the pump
All poles of the pump must be disconnected from the mains within the
switch box during insulation tests with a high-voltage generator.
The control cable (Fig. 1.1 Appendix page II) is inseparably
connected to the pump (like the mains cable).
The strain relief of the cable and impermeability against
dripping water/condensate must be ensured. If necessary,
the cable must be furnished with a drip-off loop in order to
prevent water from entering the switch box. The control
cable covers the following control functions:
Control via analogue signal 0-10V (4-core cable) (Fig. 4.2
Appendix page IV):
- Flexible wire no. 1 (brown): 0...10 V signal ground
(GND)
Flexible wire no. 2 (white): 0...10 V signal
Flexible wire no. 3 (blue): Collective fault signal
Flexible wire no. 4 (black): Collective fault signal
Collective fault signal: The collective fault signal is a floating
NC contact (closed when de-energized).
Contact load: min. permissible: 12 V DC, 10 mA,
max. permissible: 250 V AC, 1 A.
Switching frequency:
Switch-on/switch-off via line voltage
T 20 times / 24 h.
Switch-on/switch-off via 0...10 V T 20 times / h.
Min. interval between 2 operations >= 5 s
All connecting lines must be connected in such a way that
there is no contact with pipework and/or the pump/motor
casing.
Connection diagram (see Fig. 4.2 Appendix page IV)