Installation Guide
TROUBLE SHOOTING
•“EXIT” legend does not illuminate
• Checkwiringconnections.
•Emergency circuit does not work
• Batteriesareshippedunchargedanddisconnected.
Connectpowerpackleadsandchargebeforetesting.
• Makesurechargerboardisproperlyseated.
• Checkwiringconnections.
MAINTENANCE
Signsshouldbetestedandmaintainedinaccordancewith
NationalElectricalCodeandNFPA101LifeSafetyCoderequirements.
Itisrecommendedthatemergencyexitsigns
betestedfor30secondsonceamonthandfor90minutes
onceayear.
LT Tandem Series
Thermoplastic Combination Emergency
Lighting Unit/LED Exit Sign
Installation, Operation and Maintainance Instructions
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
©
HubbellLighting,Inc.,AllRightsReserved•Specificationssubjecttochangewithoutnotice.•PrintedinU.S.A. 93029201A 6/10
IMPORTANT SAFEGUARDS
Whenusingelectricalequipment,basicsafetyprecautionsshouldalwaysbefollowedincludingthefollowing.
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.Donotuseoutdoors.
2.Donotletpowersupplycordstouchhotsurfaces.
3.Donotmountneargasorelectricheaters.
4.Equipmentshouldbemountedinlocationsandatheightswhereitwillnotreadilybesubjecttotamperingby
unauthorizedpersonnel.
5.Theuseofaccessoryequipmentnotauthorizedbythemanufacturermaycauseanunsafecondition.
6.Donotusethisequipmentforotherthanitsintendedpurpose.
7.Servicingofthisequipmentshouldbeperformedbyqualifiedservicepersonnel.
8.Testcycling:theLifeSafetyCode(NFPA101)requirestestingofemergencyexitsignsonceamonthforaminimumof30secondsand
onceayearforaminimumof90minutes.
INSTALLER:
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING–ThisproductcontainschemicalsknowntotheStateofCaliforniatocausecancer,birthdefectsand/orotherreproductiveharm.
Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.
93029329
OPERATION
“ACON”LEDisiluminatedwhenACpowerispresent.
NOTE:AllmodelsaresuppliedwithanACLockoutcircuit,whichpreventsthelampsand“EXIT”legendfromilluminatingwhenthebatteryisconnectedandnoACpowerispresent.
NOTE:AllmodelsaresuppliedwithaLowVoltageDisconnectcircuit,whichpreventsdamagetothebatteryfromdeepdischargeduringprolongedemergencyoperation.
NOTE:Batteriesareoftenshippedinadischargedstate–thisisnormal.Thebatterywillrequirecharging.Allowseveralhoursofchargebeforetestingtheunit.
ModelsWithSPECTRON®Self-Testing/Self-DiagnosticCircuitry
ModelsequippedwiththeSpectronself-testing/self-diagnosticelectronicssystemprovide:
■ Visual indication of AC power status ■Visual indication of self-diagnostic test cycle
—Visual indication of any unit malfunctions including—
■ Battery fault ■ Transfer fault ■ Charger fault ■ Emergency Lamp fault
Spectron equipped units also include:
Brownout protection: unit will automatically transfer to emergency operation upon detection of low AC power (approximately 80% of nominal line).
Time Delay Retransfer: upon return of normal AC power, unit will remain in the emergency mode for an additional 15 minutes to allow AC power to stabilize.
LED Status Indicator
TwoLEDs,onegreenandonered,areprovidedonthecontrolpanelofallmodelsequippedwith
theSpectronoption.
Red Status Indicator Code Description
OneblinkON/pause Batterynotconnected
TwoblinksON/pause Batteryfault
ThreeblinksON/pause Chargerfault
FourblinksON/pause Transfercircuitfault
FiveblinksON/pause EmergencyLampfault
Automatic Tests
Theunitwillautomaticallyinitiateaself-test/self-diagnosticcyclebasedonthefollowing
table:
Testing Period Duration of Test
Onceamonth 1minute
Onceevery6months 60minutes
Manual Tests
Usingtheunittestswitch,userscaninitiatedifferentdurationtestcyclesbasedonthe
followingtable:
Initiating Action Test Cycle
Presstestswitchonce 1minute
Presstestswitchtwice 5minutes
Presstestswitchthreetimes 30minutes
Presstestswitchfourtimes 60minutes
Pressingthetestswitchatanytimeafteratestcyclehasbeguncancelstheremainderofthe
testandreturnstheunittonormaloperation.
RedServiceAlertIndicator:
Undernormaloperatingconditions,theredServiceAlertIndicatorwillremain“off”.Intheevent
theSpectroncontrollerdetectsamalfunction,theredServiceAlertIndicatorwillblinkata1Hz.
rate,basedonthefollowingtable:
GreenOperatingStatusIndicator:
ThegreenOperatingStatusIndicatorservesasbothanACpowerandaself-testindicator.During
normaloperation,thegreenOperatingStatusIndicatorwillbeilluminated,indicatingthepresence
ofACpower.Duringallautomaticormanualself-testcycles,thegreenOperatingStatusIndicator
willblinkata1Hz.rate.
MAINTENANCE
1300688
1300690
93029209
93029213
93029219
93029220
93029315
93029329
93029349
Final Assembly
1. Dresswiresneatlyto
preventpinching.
2. Alignhousingslots
overbackplatetabs.
3. Pivothousingand
snapclosed.
4. Energizeunit.Charge
aminimumof24
hourspriortotesting.
5. Presstestswitch
andhold.
Aimlampheadsfor
properlightdistribution.
6. Snapdirectional
chevronarrowplugs
intoexitstencilface
asrequired.
LAMP REPLACEMENT
CAUTION: Halogen lamps operate at high temperatures.
Allow defective lamp to cool completely before replacing.
1. Remove plastic lamp retaining ring.
2. Pull defective lamp from lighting head assembly
and unplug lamp from socket
3. Plug replacement lamp into socket and install lamp
into lighting head assembly.
4. Reinstall lamp retainer ring (flat side toward lamp).
RECYCLING INFORMATION
Allthermoplasticpartsarerecyclable.
Allcartonscontainrecycledmaterials.
Allmodelscontainnickel-cadmiumbatteries.
Pleaserecycleresponsibly.
1300688
AC ON
PUSH TO TEST
MR-16 halogen
lamp
Retaining
ring
2-pin lamp
socket
93029315