Manual

BECKETT OIL BURNER, NOZZLE, AND AIR SETTING
BOILER DELEVAN FIRING HEAD-ADJ. LOW FIRE AIR STATIC OIL
MODEL OIL NOZZLE RATE (gph) OR SETTING BAFFLE SHUTTER/BANE PLATE BURNER
3EW.65" 0.50-80° B 0.65 F0- 1 1/8 YES 10/0 3-5/8 AFG F-HEAD
3EW.75 0.65-70° B 0.75 F3- 1 1/8 YES 10/0 3-1/2 AFG F-HEAD
3EW1.00 0.85-70° B 1.00 F3 - 1 1/8 NO 10/2 3-1/2 AFG F-HEAD
4EW.90 0.75-80° A 0.90 F3 - 1 1/8 NO 8/0 3-1/2 AFG F-HEAD
4EW1.25 1.00-80°A 1.25 F6 - 1 1/8 NO 10/0 3-3/8 AFG F-HEAD
4EW1.50 1.25-80°A 1.50 F6 - 1 1/8 NO 10/2 3-3/8 AFG F-HEAD
5EW1.20 1.00-60° B 1.20 0 NO 10/1.5 2-3/4 AFG 50 MD
5EW1.75 1.50-45° B 1.75 2 NO 10/4 2-3/4 AFG 50 MD
5EW2.00 1.65-60° B 2.00 4 NO 10/5 2-3/4 AFG 50 MD
*To fire the 3EW.65 on rate, the oit pressure must be increased to 175 psig.
All Beckett oil burners for the EW boiler are factory preset at 140 psig.
CARLIN OIL BURNER, NOZZLE, AND AIR SETTING
BOILER
MODEL
3EW.65
3EW.75
3EW1.00
4EW.90
4EW1.25
4EW1.50
5EW1.20
5EW1.75
5EW2.20
DELEVAN
OIL NOZZLE
0.55-70 ° B
0.65-60 ° B
0.85-60 ° B
0.75-60 ° B
1.00-60 ° B
1.25-60 ° B
1.00-60°B
1.50-60°B
1.65-70°B
FIRING
RATE(gph)
0.65
0.75
1.00
0.90
1.25
1.50
0.20
1.75
2.00
HEAD
SETTING
0.50
0.60/0.65
0.85/1.00
0.75
0.85/1.00
1.10/1.5
0.85/1.00
1.50
1.65/1.75
AIR BAND
SET POINT
0.52
0.60
0.80
0.75
0.90
1.25
0.90
1.65
1.95
*All Carlin EZ-1 and EZ-2 HP oil burners are factory preset at 150 pslg.
CARLIN OIL BURNER, NOZZLE, AND AIR SETTING
CARLIN
BURNER*
EZ-1 HP
EZ-1 HP
EZ-1 HP
EZ-1 HP
EZ-1 HP
EZ-1 HP
EZ-1 HP
EZ-2 HP
EZ-2 HP
BOILER
MODEL
3EW.65
3EW.75
3EW 1.00
4EW.90
4EW 1.25
4EW1.50
5EW 1.20
5EW1.75
5EW2.20
*All Riello
DELEVAN
OIL NOZZLE
0.50-70 ° B
0.65-70 ° B
0.85-70 ° B
0.75-70 ° B
1.00-70 ° B
1.25-70 ° B
1.00-70°B
1.50-70°B
1.75-70°B
40 F5 and F10 oil
FIRING
RATE(gph)
0.65
0.75
1.00
0.90
1.25
1.50
1.20
1.75
2.00
TURBULATOR/AIR
SHUTTER SETTING
0.50
2.0/2.2
2.0/2.3
1.5/2.6
2.5/3.8
4.0/7.0
2.5/3.5
2.0/3.8
2.5/4.1
burner are factory preset at 145 psig.
OIL PRESSURE
(PSIG)*
155
150
170
160
170
175
150
155
155
RIELLO 40
BURNER MODEL
F5
F5
F5
F5
F5
F5
F5
F10
F10
NOTE: All burners use an insertion depth of 2-1/4" and fired at a overfire
draft of -0.02 inches w.c. The burner settings provided are intended for
initial start up only. Final adjustment must be made using combustion
test instruments.
14683006
38
REV 1, MAY 2003