rES Automatic Reset Time. Select 0FF, 0.1 to 99.9 minutes.
Select 0FF to switch to 0FS.
0FS Manual Offset correction Select. Select 0FF, 0.1 to 99.9
percent. Select 0FF to switch to rES.
rtE Rate Time. Select 0FF, 0.1 to 99.9 minutes. Derivative.
SL0 PID values are preset for a slow response process.
nor PID values are preset for a normal response process.
FASt PID values are preset for a fast response process.
Pid2 Linkage of PID parameters between SP1 and SP2: Select 0n or 0FF.
0n Applies SP1 rES, rtE, Fbnd, and FrtE terms to SP2 for heat/cool
applications
0FF SP2 functions without rES, rtE, Fbnd, and FrtE .
ArUP Anti- Reset Windup Feature: Select 0n or 0FF.
0n When ArUP is 0n the accumulated Reset Offset value will be
cleared to 0% when the process input is not within the Proportional
Band.
0FF When ArUP is 0FF, the accumulated Reset Offset value is retained
in memory when the process input is not within the Proportional
Band.
ArtE Approach Rate Time: Select 0FF, 0.01 to 99.99 minutes. The function
defines the amount of Rate applied when the input is outside of the
Proportional Band. The ArtE time and the rtE time are independent and
have no effect on each other. To increase damping effect and reduce over-
shoot set the approach rate time for a value greater than the natural rise time
of the process (natural rise time = process value time to set point).
Fint Fuzzy Logic Intensity: Select 0 to 100%. 0% is OFF (disables Fuzzy Logic).
The function defines the amount of impact Fuzzy Logic will have on the
output.
Fbnd Fuzzy Logic Error Band: Select 0 to 4000 °F, °C, or counts. Sets the band
width of the Fuzzy Logic. Set Fbnd equal to PID proportional band (Pb1) for
best results.