A1LP Alarm 1 Lamp: Select 0on or 0oFF.
0on Alarm Lamp is ON when alarm contact is closed.
0oFF Alarm Lamp is OFF when alarm contact is closed.
A1Lb Alarm 1 Loop Break. Select 0n or 0FF.
0n Loop Break Condition will cause an Alarm Condition.
0FF Loop Break will not affect the Alarm Condition.
Addr
(Option 992, 993, 995, 996, Serial Communications) Control Address: Set
from 1 to 3FF for Options 992 and 993. Set from 1 to FF for options 993
and 995. This number (hexadecimal, base 16) must match the address
number used by the host computer. Power to instrument must be turned off
and on before change takes effect (see Page14).
bAUd
(Option 992, 993, 995, 996, Serial Communications) Communication Baud
Rate: Select 300,1200, 2400, 4800, 9600 (baud), 19.2, 28.8, or 57.6
(kbaud) for Options 992 and 993. Select 300, 1200, 2400, 4800, 9600
(baud) or 19.2 (kbaud) for Options 995 and 996. This number must match
the baud rate used by the host computer. Power to instrument must be
turned off and on before change takes effect (see Page 14).
nAt
(Option 992, 993, 995, 996, Serial Communications) No Activity Timer:
Select 0FF or 1 to 99 minutes.
1- 99
Maximum time between host computer accesses. If timer counts
to 0, CHEC LorE will be displayed.
0FF
No Activity Timer function is disabled.
Stor (Option 992, 993, 995, 996 Serial Communications) Store to EEPROM:
Select
YES
or
no
. (See additional information on page 18).
YES
Menu Items changes made through the Serial Communications are
stored directly to the EEPROM.
no
Menu items changes made through the Serial Communications are
stored directly in RAM.