Manual

949-1270 Page 14 of 28 December, 1998
SECONDARY MENU
Hold UP ARROW & ENTER. Press INDEX to advance to the next menu
item. Press UP ARROW or DOWN ARROW to change the value in the
display. Press ENTER to retain the value.
SP1d Set Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S1F=Lo) or -1 to -9999 (when S1F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 1) and
the turn off point. See the following chart.
The following menu items apply only if your control is equipped with
a second set point (last digit of model number is not zero). If your
control does not have a second set point, jump to the "SP" menu item
below.
SP2d Set Point On-Off Differential (hysteresis). Select 1 to 9999 (when
S2F=Lo) or -1 to -9999 (when S2F=Hi). Set the value for the
amount of difference between the turn on point (Set Point 2) and
the turn off point. See chart above.
MENU SELECTIONS
PRIMARY MENU
Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value.
#SP1 (Option 948, 4-Stage Set Point) or
SP1 Set Point 1 Adjust, Limit Point 1.
SP2 Set Point 2 Adjust (if equipped), Limit Point 2.
ABSOLUTE ALARMS
SP1
SP2 when S2t = ABS
High Alarm
S#F = Hi
SP#
SP#
Low Alarm
S#F = Lo
DEVIATION ALARM
SP2 WHEN S2t = dE
SP1
SP2
High Alarm
S2F = Hi
Low Alarm
S2F = Lo
SP1
SP2