S1St Set Point 1 State: Select Eng or dEng.
Eng Output Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts
will close, Normally Closed contacts will open.)
dEng Output De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open
contacts will open, Normally Closed contacts will close.)
S1LP Set Point Lamp: Select O on or OoFF.
O on Lamp ON when Output is ON (energized).
OoFF Lamp OFF when Output is ON (energized).
If your instrument is not equipped with Set Point 2, then proceed to
the option section (next page). If the instrument has no Set Point 2 and
no options, then the menu ends.
S2t Set Point 2 type: Select Abs or dE.
AbS Absolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dE Deviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).
S2F Set Point 2 Function: Select Hi of Lo.
Hi Output is energized above set point.
Lo Output is energized below set point.
S2rE Set Point 2 Reset. Select OnOF or Hold.
OnOF Control will automatically reset when process passes
back through SP2d.
HoLd Manual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S2Pi Set Point 2 Power Interrupt. Select On or OFF.
On Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S2iH Set Point 2 Inhibit: Select On or OFF.
On Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF Alarm Inhibit is OFF.