User guide

Series 2900 Current to Pressure Transducer
Specifications - Installation and Operating Instructions
Bulletin V-5
The Series 2900 Current to Pressure Transducer delivers reliable
high performance for the toughest applications in the most hazardous
environments. Its NEMA 4X housing is designed and FM and CSA
approved for both intrinsically safe and explosion-proof operation. This
unit has advanced circuitry which includes electronic feedback control
for superior vibration protection and highly accurate output. The Series
2900 is not position sensitive and the easily accessible zero and span
adjustments make field calibration quick and easy. For ease of
installation, this model has input and output ports on both the front and
back. It is also not vibration sensitive, which makes the Series 2900 ideal
for field mounting on a valve. These features coupled with the unit’s
compact size help make set-up and installation simple.
SPECIFICATIONS
Service: Oil free, clean dry air filtered to 40 microns.
Input Signal: 4-20 mA.
Air Supply: Minimum: 5 psig (0.3 bar) above maximum output;
Maximum: 100 psig (6.9 bar).
Output: 3 to 15 psig (0.2 to 1.0 bar), 6 to 30 psig (0.4 to 2.1 bar).
Accuracy: ±0.1% of span.
Hysteresis: ±0.1% of span.
Repeatability: ±0.1% of span.
Deadband: 0.02% of span.
Power Requirement: Loop powered.
Temperature Limits: Operating: -40 to 160°F (-40 to 71°C); Storage: -
40 to 200°F (-40 to 93°C).
Pressure Connections: 1/4˝ female NPT.
Electrical Connection: 1/2˝ female NPT.
Air Consumption: 0.05 scfm (0.02 l/s) at midrange typical.
Output Capacity: 4.5 scfm (2.1 l/s) at 25 psig (1.7 bar) supply; 12.0
scfm (5.7 l/s) at 100 psig (6.9 bar) supply.
Enclosure: Chromate-treated aluminum with epoxy paint.
Enclosure Rating: Weatherproof NEMA 4X (IP65), Explosion-proof
and intrinsically safe.
Weight: 1.8 lb (0.82 kg).
Agency Approvals: CE, CSA, FM.
1/2 NPT PORT FOR
CONDUIT PIPING
4-19/32
(116.6)
2-5/64
(52.6)
33/64
(13.1)
1
-1/2
(
38.1)
4
9/64
(
19.4)
4 #10-32-UNF
TAPPED HOLES FOR
MOUNTING
Ø3-1/2
(Ø88.9)
1
(25.4)
2
7/32
(
21.3)
2
-1/2
(
63.5)
2-3/16
(55.6)
5
7/64
(
22.4)
IN & OUT
PORTS 1/4-18 NPT
4 PLACES
Model
2913-E
2916-E
Input
4-20 mA
4-20 mA
Output
3-15 psig (0.2-1.0 bar)
6-30 psig (0.4-2.1 bar)
PROXIMITY CONTROLS
Phone: 219/879-8000 www.dwyer-inst.com
A DIVISION OF DWYER INSTRUMENTS, INC.
Fax: 219/872-9057 e-mail: info@dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A.

Summary of content (4 pages)