Manual

Chapter 4 Installation
4.1 Overview
The information in Chapter 4 explains installation.
4.2 Safety Message
Procedures and instructions in this chapter may require special
safety measures to ensure the safety of the personnel performing
the operation. Potential installation safety issues are indicated by a
warning symbol (▲). Refer to the following safety messages before
installing the 3200 pressure transmitter.
4
.3 Warning
4.4 Commissioning on the Bench with Hand-Held Terminal
The 3200 Pressure Transmitter can be commissioned before and
after installation. Commissioning is easier if the transmitter is
configured on a bench with an HHT before installation.
4.5 General Considerations
The transmitter can be mounted near the process to minimize piping.
Keep in mind that easy access is required for personnel, field
calibration, and installation. Install the transmitter in an area with
minimal vibration, shock, and temperature fluctuations.
4.6 Electrical Considerations (Power Supply)
The transmitter housing is composed of two parts. One side is
electronics, and the other side is terminal block. The terminal block
side is the transmitter's front side and is labeled “Field Terminal" on
the housing. The terminal block can be accessed by removing the
front cover. When wiring the power supply to the transmitter make
sure the positive and negative wires are connected correctly.
A HHT configurator can be connected directly across the (COMM)
pin terminal located just below the power supply (PWR) terminal
block connections.
4.6.1 Power Supply
The 3200 Pressure Transmitter requires an 11.9 - 45 VDC power
supply. A 250 ~ 550Ω (24 VDC) loop resistance is recommended
for HART
®
communication.
Loop resistance is the sum of the resistance in the loop.
Max. Loop Resistance [Ω] = (E-11.9) [vdc] / 0.022 [mA]
Page 10
Do you want
Basic Setup
a) Unit Setup
b) Range Setup
c) Dampening Setup
d
) Transmitter Function Setup
S
tart
Verify
a
) Pressure Support
Y
es
End
Field Install
a
) Jumper/Switch Setup
b) Transmitter takes up
c
) Transmitter leads
d) Transmitter for Power Supply
Do you satisfy spec? Maintenance
No
Figure 4-1 Installation Flow Chart
Explosion can result in death or serious injury:
• Do not remove the transmitter covers in an explosion-proof environment when the
c
ircuit is powered.
Both transmitter covers must be fully engaged to meet the explosion-proof
r
equirements.
W
ARNING
E
lectrical shock can result in serious injury:
Only qualified personnel can wire the pressure transmitter.
WARNING
P
rocess leaks can cause death or serious injury:
• Install and tighten before applying pressure. If you don’t, it can
cause process leaks.
W
ARNING
Electrical shock can result in death or serious injury:
• Avoid contact with the leads and terminals.
W
ARNING