Owner's manual

Bulletin V-9
Specifications - Installation and Operating Instructions
Series GV Globe Control Valves
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 MICHIGAN CITY, INDIANA 46360 U. S.A.
Phone: 219/879-8000 www.dwyer-inst.com
Fax: 219/872-9057 e-mail: info@dwyermail.com
The Series GV globe valves provide excellent throttling control in a wide
variety of applications. The forged brass body construction is designed
to withstand the harsh working conditions associated with many flow
control systems, with high temperature models available to fully encom-
pass the spectrum of these environments. 2 and 3-way body styles and
a variety of valve sizes are offered for various application needs.
INSTALLATION
1. Before mounting the valve, make sure that the pipe is clean and free
from any soldering scraps, sheet metal, sand, stone, or other sun-
dries.
2. The pipe and valve body must be connected perfectly, with minimal
vibration at the installation point. The direction of the flow media
should be the same as marked on the valve body.
3. The actuator should be mounted vertically on the valve body. Do not
mount the actuator below the valve body.
4. Power to the actuator must be shut off before attempting valve main-
tenance. Depressurize the piping system prior to valve servicing.
5. For other installation requirements, please refer to the Installation
and Operating Instructions for the Series EVA electric actuator,
Bulletin V-7 for EVA1 models, V-8 for EVA2 and EVA3 models.
SPECIFICATIONS
GV1
Service: Compatible liquids and gases.
Line Size: 1˝ to 2˝.
Body Style: 2-way, push to open globe; 3-way globe.
End Connections: 1˝ to 2˝ female NPT.
Pressure Limit: 232 psi (16 bar).
Wetted Materials:
Body Material: Brass;
Stem: 302 SS;
Disc: Brass with Nitrile gasket;
Packing: Fluon
®
filler with Nitrile O-ring.
Temperature Limits: 35 to 201°F (2 to 94°C).
Flow Characteristic: Equal percentage.
Flow Leakage: Less than 0.05% of Cv factor.
Stem Connection: M8 thread.
GV2/GV3
Service: GV2: Compatible liquids and gases.
GV3: Compatible liquids, gases, and steam.
Line Size: 1˝ to 2-1/2˝.
Body Style: 2-way, push to open globe; 3-way globe.
End Connections: 1˝ to 2-1/2˝ female NPT.
Pressure Limit: 232 psi (16 bar) WOG; GV3: 130 psi SWP.
Wetted Materials:
Body Material: Brass.
Stem: SS (1Cr18Ni9).
Disc: GV2: Brass with Nitrile gasket.
GV3: Brass with Fluon
®
gasket.
Packing: GV2: Fluon
®
filler with Nitrile O-ring.
GV3: Fluon
®
filler with Fluorine O-ring.
Temperature Limits: GV2: 35 to 201°F (2 to 94°C), GV3: 35 to 356°F
(2 to 180°C).
Flow Characteristic: Equal percentage.
Flow Leakage: Less than 0.05% of Cv factor.
Stem Connection: M8 thread.
C
B
A
G
V1
GV1
GV2/GV3
GV2 & GV3
C
B
A
DIMENSIONS
Model
GV121
GV122
GV123
GV124
GV131
GV132
GV133
GV134
Fluon
®
is a registered trademark of AGC Chemicals Americas, Inc.
A
4-11/32˝ (110 mm)
4-47/64˝ (120 mm)
5-1/8˝ (130 mm)
5-23/32˝ (145 mm)
4-11/32˝ (110 mm)
4-47/64˝ (120 mm)
5-1/8˝ (130 mm)
5-23/32˝ (145 mm)
B
2-3/8˝ (60 mm)
2-39/64˝ (66 mm)
2-11/16˝ (68 mm)
2-27/32˝ (72 mm)
3-5/64˝ (78 mm)
3-15/64˝ (82 mm)
3-15/64˝ (82 mm)
3-19/32˝ (91 mm)
C
4-3/8˝ (111 mm)
4-3/8˝ (111 mm)
4-1/2˝ (114 mm)
4-31/32˝ (126 mm)
4-3/8˝ (111 mm)
4-3/8˝ (111 mm)
4-1/2˝ (114 mm)
4-31/32˝ (126 mm)
Model
GV221/321
GV222/322
GV223/323
GV224/324
GV225/325
GV231/331
GV232/332
GV233/333
GV234/334
GV235/335
A
4-11/32˝ (110 mm)
4-47/64˝ (120 mm)
5-1/8˝ (130 mm)
5-23/32˝ (145 mm)
4-11/32˝ (110 mm)
4-47/64˝ (120 mm)
5-1/8˝ (130 mm)
5-23/32˝ (145 mm)
5-1/8˝ (145 mm)
6-29/32˝ (175 mm)
B
2-31/64˝ (63 mm)
2-23/32˝ (69 mm)
2-13/16˝ (71 mm)
3-3/64˝ (77 mm)
3-9/32˝ (83 mm)
3-13/64˝ (81 mm)
3-23/64˝ (85 mm)
3-23/64˝ (85 mm)
3-51/64˝ (96 mm)
4-7/64˝ (104 mm
C
4-17/64˝ (108 mm)
4-17/64˝ (108 mm)
4-3/8˝ (111 mm)
4-1/2˝ (114 mm)
4-25/32˝ (121 mm)
4-17/64˝ (108 mm)
4-17/64˝ (108 mm)
4-3/8˝ (111 mm)
4-1/2˝ (114 mm)
4-25/32˝ (121 mm)

Summary of content (2 pages)