User Manual

The SVP Series is a low cost, uniquely designed solenoid valve which
controls or regulates flow in proportion to a variable voltage input. While
most solenoid valves simply provide on/off service, this unit adds a total-
ly new dimension to solenoid valve performance. Reacting to a 0-24
VDC input signal, the valve opens proportional to the voltage applied,
delivering just the right amount of flow needed. Compatible with a wide
rage of gases and liquids, this unit provides the solution to even the most
demanding applications like process control, chemical mixing, high tech
manufacturing and laboratory testing. Another quality feature of this
valve is its tight shut-off (NC) when de-energized.
INSTALLATION
Select a location which is free of excessive heat, moisture and vibration.
The series SVP Proportioning Solenoid Valve may be held in place by
your 1/4˝ metal process tubing or secured to a rigid surface via the two
6-32 tapped holes in the base of the valve body. Flow through the valve
should be in the direction of the arrow marked on the body. The Series
SVP Valve may be used with most gases or liquids that are compatible
with the wetted parts: 316 and 416 stainless steel and Fluoroelastomer.
Due to the small orifice size of the Series SVP, the media must be free
of scale, particulate, or any other contaminant’s which might interfere
with the motion of the valve.
SPECIFICATIONS
Voltage Input: 0-24 VDC.
Maximum Operating Current: 400 mA.
Electrical Connections: Male spade type.
Wetted Materials: 316 and 416 stainless steel, Fluoroelastomer,
O-rings.
Maximum Pressure: 500 psig (34.45 bar).
Process Temperature Limits: -40°F to 174°F (-40°C to 79°C).
Ambient Temperature Limits: -40°F to 130°F (-40°C to 54°C).
Type of Operation: Normally closed, valve will close when de-ener-
gized.
Connections: 1/4˝compression fitting.
Weight: 12 oz. (340 grams).
The precise flow characteristics of each valve will vary depending on a
number of factors, including orifice size and upstream pressure. While it
is best to determine valve performance under your own process condi-
tions, the flow curve shown in Fig. A can be used for reference purpos-
es.
Series SVP Proportioning Solenoid Valve
Specifications - Installation and Operating Instructions
Bulletin F-82
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9052 e-mail: info@dwyermail.com
©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 4/14 FR# RV-440894-00 Rev. 2
Stocked Models:
Model
SVP-1
SVP-2
SVP-3
SVP-4
Orifice
IN. (MM)
0.020 (0.51)
0.040 (1.02)
0.055 (1.40)
0.063 (1.60)
C
V
0.009
0.033
0.055
0.068
Air
SCFH (LPM)
7.4 (3.5)
27.5 (13)
45.6 (21.5)
53 (25)
Water
GPH (CC/M)
2.0 (125)
6.4 (400)
11.1 (700)
13.5 (850)
Maximum Flow*
SOLENOID VALVE PSV
FLOW IN FUNCTION WITH VALVE VOLTAGE 
VOLTAGE TOLERANCE FOR DIFFERENT VALVE SIZES.
FLOW
%
FOR 10 PSID
VOLTS
(TOLERANCE
±1.25 VOLTS)
10
20
30
40
50
60
70
80
90
100
4
5
6
7
89101112
13 14 15 16
*Based on 10 psig (69 kPa) inlet pressure and atmospheric exhaust.
Fig. A

Summary of content (1 pages)