Owner manual

Series TID Temperature/Process Indicator
Specifications - Installation and Operating Instructions
Bulletin E-90-TID
The affordable Series TID allows user to monitor
temperature or a process value. Temperature ranges are
available from -58 to 302°F using one of our PTC or NTC
thermistors. Process values can be displayed from -999 to
999 counts using a 4 to 20 mA signal from one of our
various transmitters. The process indicator has an
adjustable span and zero on the 4 to 20 mA models.
Installation
Note: Unit must be mounted away form vibration, impacts,
water, and corrosive gases.
• Cut hole in panel 2.80 x 1.14 in (71 x 29 mm).
• Apply silicone (or rubber gasket) around the perimeter of
the hole to prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until
secure to panel.
• Remove back cover to wire unit.
• Wiring diagram is displayed on the top of the unit.
SPECIFICATIONS
Inputs: PTC/NTC thermistor or 4 to 20 mA.
Display: 3-digits; red, green or blue display.
Range: -58 to 302°F (thermistor); -999 to 999 counts (4
to 20 mA).
Power Requirements: 110 VAC, 230 VAC, 12 VAC/DC,
24 VAC/DC.
Accuracy: Better than 1%.
Resolution: 1° or 0.01 count.
Front Panel Rating: IP64.
Agency Approvals: CE.
THERMISTOR CONNECTION DIAGRAM
LOVE CONTROLS DIVISION
Phone: 219/879-8000 www.love-controls.com
DWYER INSTRUMENTS INC.
Fax: 219/872-9057 e-mail:love@love-controls.com
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.
E-90-TID 5/25/07 3:47 PM Page 1