Installation Guide

4
GENERAL SAFETY INFORMATION
LOCATING HEATER
Improper installation or failure to follow the procedures outlined in this
instruction manual can result in serious electrical shock.
WARNING
Figure 2
6. All electrical power must be disconnected at the main service box, which
must be locked before connecting, inspecting, cleaning or servicing the
heater. This is an important precaution to prevent serious electric shock.
7. This heater is not suitable for use in hazardous locations containing
explosive
liquids or vapours. This heater has hot or arcing or sparking pads
inside. Do not use it in areas where gasoline, paint or ammable liquids are
used or stored.
8. This heater is not suitable for use in corrosive atmospheres or chemical
storage areas.
9. This heater must be mounted at least 8 feet off the oor. For specic
clearances, please see next page.
Install heater away from trafc areas, maintaining clearances stated in Figure 2
(below). The air ow direction should not be restricted (ie. by columns or
machinery). The air ow should not blow directly at exposed walls. When more
than one heater is used in an area, heaters should be installed so that the air
discharge of each heater supports the air flow of the others, to provide best
warm air circulation as shown in Figure 3 (see page 5).