2/25Motoren schalten und schützen CA034001DE – Dezember 2017 www.eaton.eu
Motorschutzrelais
UL/CSA Kurzschlussfestigkeit
2.6
Moeller series
2
Basic Rating
SCCR max. Fuse max. CB
1)
kA A A
ZE-0,16 5 1 15
ZE-0,24 5 1 15
ZE-0,4 5 1 15
ZE-0,6 5 1 15
ZE-1,0 5 3 15
ZE-1,6 5 6 15
ZE-2,4 5 6 15
ZE-4 5 15 15
ZE-6 5 20 15
ZE-9 5 35 15
ZE-12 5 45 16
ZB32-38 5 150 -
ZB65-10 5 40 40
ZB65-16 5 60 60
ZB65-24 5 90 90
ZB65-40 5 125 125
ZB65-57 10 200 150
ZB65-65 10 200 150
ZB65-75 10 200 150
ZB150-35 5 125 125
ZB150-50 5 225 200
ZB150-70 10 250 250
ZB150-100 10 400 Class J 400
ZB150-125 10 500 Class J 500
ZB150-150 10 600 Class J 600
ZB150-175 10 600 Class K5 600
ZB150-35/KK 5 60 Class J
ZB150-50/KK 5 110 Class J
ZB150-70/KK 10 125 Class J
ZB150-100/KK 10 200 Class J
ZB150-125/KK 10 250 Class J
ZB150-150/KK 10 300 Class J
ZB150-175/KK 10 300 Class J
Z5-70 10 250 250
Z5-100 10 400 Class J 400
Z5-125 10 500 Class J 500
Z5-160 10 600 Class J 600
Z5-220 10 800 Class L 800
Z5-250 18 1200 Class L 1200
Z5-300 18 1200 Class L 1200
1)
bei ZE-…: CB für max. 480 V
480 V High Fault 600 V High Fault
SCCR (fuse) max. Fuse SCCR (CB) max. CB SCCR (fuse) max. Fuse
kA A kA A kA A
ZB12(32)-0,16 100 1 Class J/CC
ZB12(32)-0,24 100 1 Class J/CC
ZB12(32)-0,4 100 1 Class J/CC
ZB12(32)-0,6 100 1 Class J/CC
ZB12(32)-1 100 1 Class J/CC
ZB12(32)-1,6 100 3 Class J/CC
ZB12(32)-2,4 100 3 Class J/CC
ZB12(32)-4 100 6 Class J/CC
ZB12(32)-6 100 10 Class J/CC
ZB12(32)-10 100 15 Class J/CC
ZB12-12 100 15 Class J/CC
ZB12-16 100 30 Class J/CC
ZB32-16 100 35 Class J
ZB32-24 100 45 Class J
ZB32-32 100 60 Class J
ZB65-10 100 15 Class J/CC 65 15 100 15 Class J/CC
ZB65-16 100 35 Class J/CC 65 25 100 35 Class J/CC
ZB65-24 100 45 Class J/CC 65 50 100 45 Class J/CC
ZB65-40 100 60 Class J/CC 65 60 100 60 Class J/CC
ZB65-57 100 110 Class J/CC 65 75 100 110 Class J/CC
ZB65-65 100 125 Class J/CC 65 100 100 125 Class J/CC
ZB65-75 100 125 Class J/CC 65 100 100 125 Class J/CC