Data Sheet

DATASHEET - FRBM6-B16/3N/003-A
RCD/MCB combination, 16 A, 30 mA, MCB trip characteristic: B, 3p+N,
RCD trip characteristic: A
Part no. FRBM6-B16/3N/003-A
Catalog No. 170988
Alternate Catalog
No.
FRBM6-B16/3N/003-A
Similar to illustration
Delivery program
Basic function Combined RCD/MCB devices
Number of poles 3 pole+N
Tripping characteristic B
Application Switchgear for industrial and advanced commercial applications
Rated current I
n
A 16
Rated switching capacity according to IEC/EN 61009 kA 6
Rated fault current I
ΔN
A 0.03
Type Type A
Tripping s… non-delayed
Product range FRBm6
Sensitivity Pulse-current sensitive
Impulse withstand current Partly surge-proof 250 A
Contact sequence
Technical data
Electrical
Protected pole 4
Rated voltage according to IEC/EN 60947-2 U
n
V AC 240
Rated frequency f Hz 50
Rated fault current I
Δn
mA 30
Sensitivity Pulse-current sensitive
Rated current I
n
A 16
Tripping characteristic B
Standards EN 45545-2; IEC 61373
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 16
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 3.6
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 40
0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
06/16/2021 Eaton 170988 ED2021 V80.0 EN 1 / 3