Data Sheet

10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination (ecl@ss10.0.1-27-14-22-07
[AFZ810015])
Number of poles (total) 4
Number of protected poles 4
Rated voltage V 415
Rated insulation voltage Ui V 500
Rated impulse withstand voltage Uimp kV 4
Rated current A 16
Rated fault current A 0.03
Leakage current type A
Current limiting class 3
Rated short-circuit breaking capacity acc. EN 61009 kA 6
Rated short-circuit breaking capacity IEC 60947-2 kA 6
Rated short-circuit breaking capacity Icn acc. EN 61009-1 kA 6
Disconnection characteristic
Surge current capacity kA 0.25
Voltage type AC
Frequency 50 Hz
Release characteristic B
Concurrently switching N-neutral Yes
With interlocking device No
Over voltage category 3
Pollution degree 2
Ambient temperature during operating °C -25 - 40
Width in number of modular spacings 4
Built-in depth mm 75.5
Suitable for flush-mounted installation No
Anti-nuisance tripping version No
Degree of protection (IP) IP20
Connectable conductor cross section solid-core mm² 1 - 25
Connectable conductor cross section multi-wired mm² 1 - 25