Data Sheet

DATASHEET - FRCMM-125/4/003-B
Residual current circuit-breaker, all-current sensitive, 125 A, 4p, 30 mA,
type B
Part no. FRCMM-125/4/003-B
Catalog No. 171184
Alternate Catalog
No.
FRCMM-125/4/003-B
EL-Nummer
(Norway)
1666601
Similar to illustration
Delivery program
Basic function Residual current circuit-breakers
Number of poles 4 pole
Application Switchgear for industrial and advanced commercial applications
Rated current I
n
A 125
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Rated fault current I
ΔN
A 0.03
Type Type B
Tripping s… non-delayed
Product range FRCmM-125
Sensitivity All current sensitive
Impulse withstand current Partly surge-proof 250 A
Contact sequence
Technical data
Electrical
Types conform to IEC/EN 61008
Standards IEC/EN 61008
Current test marks As per inscription
Tripping s… Short-time delayed
Rated voltage according to IEC/EN 60947-2 U
n
V AC 240/415
Rated frequency f Hz 50
Limit values of the operating voltage
Test circuit V AC 184 - 440
Rated fault current I
Δn
mA 30
Sensitivity All current sensitive
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4 (1.2/50μs)
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Impulse withstand current 3 kA (8/20 μs) surge-proof
Max. admissible back-up fuse
Short-circuit gG/gL A 125
Overload gG/gL A 80
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 1250
lifespan
Electrical Operations ≧ 4000
06/18/2021 Eaton 171184 ED2021 V80.0 EN 1 / 4