Data Sheet

DATASHEET - XNH00-S160-BT1
NH fuse-switch 3p box terminal 1,5 - 95 mm²; busbar 60 mm; NH000 &
NH00
Part no. XNH00-S160-BT1
Catalog No. 183034
EL-Nummer
(Norway)
1624009
Delivery program
Basic function Basic device
Number of poles 3 pole
Mounting type Busbars of 60 mm
Size 00
Type of connection Box terminal
Rated operational current I
e
A 160
Front degree of protection (XNH installed) IP20 (Operating status)
IP2XC (Contact protection)
IP10 (Handle cover open)
Rated operational voltage U
e
V AC 690
Rated operational voltage U
e
V DC 440
Rated conditional short-circuit current kA 120 (500 V)
100 (690 V)
Flammability characteristics Self-extinguishing as per UL 94
Description Current paths of electrolytic copper, silver-plated
Cable connection optionally at the top or bottom
Successor to 224550
120603
Technical data
Electrical
Standards IEC/EN 60947-3
Rated operational voltage U
e
V AC 690
Rated operational voltage U
e
V DC 440
Rated operational current I
e
A 160
Rated frequency f Hz 40 - 60
Rated insulation voltage U
i
V AC 800
Total heat dissipation at I
th
(without fuses) P
v
W 14
Heat dissipation at 80% (without fuses) P
v
W 9
Rated impulse withstand voltage U
imp
kV 8
Utilization category AC-23B
Rated operating voltage U
e
V AC 400
Rated operating current I
e
A 160
Utilization category AC22B
Rated operating voltage U
e
V AC 500
Rated operating current I
e
A 160
Utilization category AC-21B
Rated operating voltage U
e
V AC 690
Rated operating current I
e
A 160
Utilization category DC-22B
Rated operating voltage U
e
V DC 250
Rated operating current I
e
A 160
Utilization category DC21B
Rated operating voltage U
e
V DC 440
Rated operating current I
e
A 160
Rated conditional short-circuit current kA 120 (500 V)
06/18/2021 Eaton 183034 ED2021 V80.0 EN 1 / 4