Data Sheet

100 (690 V)
Rated short-time withstand current I
cw
kA 7
Max. fuse
Size according to DIN VDE 0636-2 000 / 00
Max. permitted power loss per fuse link P
v
W 12
Lifespan, electrical Operations 300
Mechanical
Front degree of protection (XNH installed) IP20 (Operating status)
IP2XC (Contact protection)
IP10 (Handle cover open)
Ambient temperature °C -25 - +55
Rated operating mode Permanent operation
Activation Dependent manual activation
Mounting position Vertical, horizontal
Altitude m Max. 2000
Overvoltage category/pollution degree III/3
RoHS (in accordance with Directive 2002/95/EC of the European Parliament and
Council)
Yes
Direction of incoming supply as required (FLEX System)
Lockable Yes, optional
Sealable Yes, Standard
Material characteristics
Material Polyamide
Colour Grey
Flammability characteristics Self-extinguishing as per UL 94
Halogen-free Yes
Voltage test Yes, sliding inspection windows
Lifespan, mechanical Operations 1400
Track resistance CTI 600
Heat deflection temperature °C 125
Terminal capacity
Flange connection
Bolt diameter M8
Cable lug max. width mm 25
Flat busbar mm 20 x 10
Box terminal
Stranded
mm
2
1,5 - 95 Cu
Copper strip Number of
segments
x width x
thickness
mm 9 x 9 x 0,8
Box terminal
Stranded
mm
2
1,5 - 50 Cu
Copper band Number of
segments
x width x
thickness
mm 6 x 9 x 0,8
Clamp-type terminal
Stranded
mm
2
10 - 70 Cu/Al
Double clamp-type terminal
Stranded
mm
2
-
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 160
Heat dissipation per pole, current-dependent P
vid
W 4.7
Equipment heat dissipation, current-dependent P
vid
W 14
IEC/EN 61439 design verification
06/18/2021 Eaton 183034 ED2021 V80.0 EN 2 / 4