Data Sheet

DATASHEET - PXK-C6/1N/003-A
RCD/MCB combination, 6 A, 30 mA, MCB trip characteristic: C, 1p+N, RCD
trip characteristic: A
Part no. PXK-C6/1N/003-A
Catalog No. 236961
Similar to illustration
Delivery program
Basic function Combined RCD/MCB devices
Number of poles 1 pole+N
Tripping characteristic C
Application Switchgear for residential and commercial applications
Rated current I
n
A 6
Rated switching capacity according to IEC/EN 61009 kA 10
Rated fault current I
ΔN
A 0.03
Type Type A
Tripping s… non-delayed
Product range PXK
Sensitivity Pulse-current sensitive
Impulse withstand current Partly surge-proof 250 A
Technical data
Electrical
Sensitivity Pulse-current sensitive
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 1.7
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 40
0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
06/18/2021 Eaton 236961 ED2021 V80.0 EN 1 / 2