Operating Guide

29
PLEASE NOTE: 20H IS FOR OUTDOOR PERMANENT INSTALLATIONS ONLY AND 20HI IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL
AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
English
Installing the 20HI water heater, Continued....
Venting Lengths
MAXIMUM VENT LENGTH
Owner must refer to vent manufacturer’s instructions and specications. Z-Flex information can be
found at www.novaex.com, please refer to page 32 for additional links.
The system will not operate if there is excessive restriction (pressure drop)
in the venting system. A maximum of 32 feet of vent pipe may be used
provided there is only one 90° elbow in the system. If additional elbows are
required: two elbows can be used with 27 feet, and three elbows can be used
with 22 feet of vent pipe.
A 90° elbow is equivalent to 5 feet of straight pipe. A 45° elbow is equivalent
to 2 feet 6 inches of straight pipe .
The termination elbow does not count as an elbow when determining total
vent lengths.
The vent must be installed with a slight downward slope of 1/ 4” per
foot of horizontal run toward the vent terminal (see diagram below). This
ensures that any condensate formed during operation of the water heater is
evacuated from the water heater.
A 1/4” per foot upward slope is acceptable when it is not possible to vent
with a downward slope, however, a UL approved Category III Stainless Steel
condensate trap MUST be installed at the beginning of the horizontal run
(See page 33 “Typical Horizontal Termination w/ 1/4” per foot UPWARD
Slope” or page 33, “Standard Vertical Vent Termination” for examples).
Number of
90° elbows
(bends)
Maximum
Length of
Straight Pipe
1
2
3
32’
27’
22’
One (1) 90° Elbow is
Equivalent to 5 Feet of
Straight Pipe
MINIMUM VENT LENGTH
The venting may be as short as 12”,
provided one vent termination is
installed to the outdoors through a
sidewall, one 90°elbow is included
in the installation, and the wall
thimble is installed.
NOTICE: Make sure that the seam
of the vent pipe in horizontal runs
is toward the top of the installation
(see illustration to the left)
Draining the Condensate
In certain conditions, installations in unconditioned space or having long horizontal or vertical
runs may accumulate condensate.
Condensate is known to be acidic; refer to local, state (provincial) or federal codes for proper
handling methods.
In order to prevent condensate from draining back into the water heater, we recommend a
condensate trap and drain to be installed in a horizontal vent section as close as practical to
the water heater vent connection.
Not following proper condensate procedures will void warranty.
20HI Installation
Vent Seam
1/4” per foot
downward slope
More than 6”
12 in.
minimum